Electrical Engineering › Section Y · Time-varying fields, Maxwell's equations, and plane waves › Topic Y.4
Transformers and the electric generator from field theory
The transformer and the generator were met earlier as circuit devices. Here both fall straight out of the field form of Faraday's law: transformer emf in one case, motional emf in the other, with the polarity rules and the low-frequency limits made explicit.
A transformer from Faraday's law
Wind two coils, of \(N_1\) and \(N_2\) turns, on one high-permeability core, so that the same flux \(\Phi\) passes through every turn of both. Drive coil 1 with a sinusoidal source; its current sets up a changing flux in the core, and that flux induces a voltage in coil 2. Write Faraday's law for each coil, with each coil's normal pointing along the core flux:
The flux derivative is common to both, so dividing gives \(v_1/v_2 = N_1/N_2\) at every instant, and the phasors obey \(V_1/V_2 = N_1/N_2\) too. This is the turns-ratio law of "The iron-core transformer and power transmission", now derived from the field equation rather than assumed.
Winding sense sets the sign
The derivation assumed both coils were wound the same way round the core. Reverse the winding of coil 2 and, for the same terminal labels, its right-hand normal points against the core flux, so its voltage changes sign. Both cases fit one expression:
with \(p = +1\) for windings in the same sense and \(p = -1\) for opposite senses. With coil 1 as the primary, \(N_1/N_2\) is the course's ratio a. On a schematic, where windings cannot be seen, the dot convention of "Equivalent circuits, coupled coils, and air-core transformers" records the same information: dotted terminals rise together.
Why cores are often toroids
A straight core lets flux spill out of its ends and loop through the surrounding space. A ring-shaped, or toroidal, core gives the flux a closed path entirely inside the material, so almost none leaks out. That improves coupling between the windings, and it matters for electromagnetic compatibility too: a toroid's field barely reaches neighbouring circuits, and stray fields from outside barely disturb the flux that links its coils. The operating principle is unchanged; only the confinement is better.
The transformer as a two-port
Treat the ideal transformer as a box with an input port and an output port, with the secondary current \(I_2\) taken as leaving the + terminal into a load \(Z_L\). With no winding resistance and no leaked flux, power in equals power out, \(V_1I_1 = V_2I_2\), so \(I_1/I_2 = V_2/V_1 = p\,N_2/N_1\). The impedance seen at the input is then
The factor p appears in both the voltage and the current ratios and cancels, so the impedance transformation does not depend on winding sense. This is the \(a^2\) rule of "Reflected impedance and impedance matching".
Why transformers fail at low frequency
Rearranging Faraday's law for coil 1 gives the flux from the applied voltage:
At dc the flux is steady, so nothing is induced in the secondary. For a sinusoid of rms value V, the integral gives a peak flux \(\Phi_m = \sqrt{2}\,V/(\omega N_1)\), which grows as the frequency falls. Real core materials saturate: beyond a certain flux density they stop responding in proportion, the magnetising current soars, and transformer action breaks down. So a practical transformer behaves as a high-pass device, working well above some lowest frequency set by its turns and core area.
Worked example: running at half frequency
A transformer primary has 300 turns on a core of cross-section 30 cm² and is rated for 230 V at 50 Hz. Find the peak flux density, then repeat at 25 Hz. 1. Peak flux at 50 Hz:
2. Flux density, with \(A = 3.0 \times 10^{-3}\,\text{m}^2\): \(B_m = \Phi_m/A = 1.15\,\text{T}\), comfortable for silicon steel. 3. At 25 Hz the same voltage needs twice the flux, so \(B_m = 2.30\,\text{T}\), above the roughly 1.5 to 2 T at which steels saturate. 4. Check: the 4.44 form gives \(230/(4.44 \times 50 \times 300) = 3.45\,\text{mWb}\) as well. The core would saturate unless the voltage were halved too.
Isolation and baluns
Because only changing flux couples the windings, a transformer blocks dc and slowly varying offsets while passing the signal. There is no conducting path between the windings, so the two circuits can sit at different dc levels, which also breaks ground loops. The same property lets a transformer act as a balun, short for balanced to unbalanced: it converts a single-ended signal, referenced to ground, into a differential pair with no ground connection, or back again. Baluns of this kind connect coaxial cable to dipole antennas and to differential amplifier inputs, and a transformer balun's advantage is that it works over a wide bandwidth.
The generator: a loop turning in a field
Now hold the field steady and move the loop instead: motional emf. A flat N-turn coil of area A turns at angular speed \(\omega\) in a uniform field B, and its normal sweeps round so that the angle between \(\hat{\mathbf{n}}\) and the field is \(\omega t\). The flux per turn is \(\Phi = BA\cos\omega t\), and Faraday's law gives
The peak, \(NBA\omega\), occurs when the coil's plane lies along the field, where the flux is zero but changing fastest. The voltage is zero when the coil faces the field squarely, where the flux is greatest. Turning the field magnet past fixed coils gives the same result, which is how most large alternators work.
Worked example: a small alternator
A 100-turn rectangular coil, 10 cm by 12 cm, turns at 3600 rpm in a uniform 0.25 T field. Find the frequency, the peak voltage and the rms voltage. 1. Speed: 3600 rpm is 60 revolutions per second, so \(f = 60\,\text{Hz}\) and \(\omega = 377\,\text{rad/s}\). 2. Area: \(A = 0.10 \times 0.12 = 0.0120\,\text{m}^2\). 3. Peak:
4. Rms: \(113/\sqrt{2} = 80.0\,\text{V}\), so the output is \(v = 113\sin(377t)\,\text{V}\) if timing starts with the coil facing the field. Check: halving the speed halves both the frequency and the voltage, because \(\omega\) appears in both.
Common mistakes to avoid
First, forgetting that winding sense can flip the sign of a voltage ratio, while impedance scaling never changes sign. Second, expecting a transformer to pass dc, or to work at any low frequency at full voltage; the flux grows as 1/f until the core saturates. Third, placing the generator's peak voltage where the flux is greatest; it occurs where the flux is zero. Fourth, using revolutions per minute directly as \(\omega\); convert to revolutions per second, then multiply by \(2\pi\).
Key takeaways
Applying Faraday's law to two coils sharing one flux gives \(V_1/V_2 = p\,N_1/N_2\), with p = ±1 for winding sense. Power balance gives the inverse current ratio and \(Z_1 = (N_1/N_2)^2 Z_L\), independent of p. Toroids confine the flux. The flux is the integral of the voltage, so dc does not transform and low frequencies saturate the core: transformers are high-pass, which also lets them isolate and act as baluns. A coil turning in a steady field gives \(v_T = NBA\omega\sin\omega t\), peaking where the flux is zero.
Flashcards
Flashcard
One core flux Φ links every turn of both windings
Test your understanding
Question 1 of 5
An ideal transformer has N₁/N₂ = 4 and an 8.0 Ω resistive load on the secondary. What resistance is seen at the primary?
Question 2 of 5
Coil 2 of a transformer is rewound in the opposite sense, keeping the same terminal labels. What changes?
Question 3 of 5
A 200-turn winding is driven at 120 V rms, 60 Hz. What is the peak core flux?
Question 4 of 5
A transformer's supply is changed from 60 Hz to 30 Hz at the same rms voltage. What happens to the peak core flux?
Question 5 of 5
A 50-turn coil of area 0.020 m² turns at 1500 rpm in a uniform 0.50 T field. What is the peak voltage?