Electrical Engineering › Section M · Transformers and polyphase systems › Topic M.2
The iron-core transformer and power transmission
An iron-core transformer changes an ac voltage up or down with almost no loss, using nothing but two windings and a shared core. That one ability is why power grids run on alternating current and send energy hundreds of kilometres at very high voltage.
The ideal iron-core transformer
Wind a primary and a secondary on one closed core of laminated steel. The core guides almost all the flux through both windings, so the coefficient of coupling from "Mutual inductance" is very close to 1. To find the main relationships, assume an ideal transformer: k = 1, so the same mutual flux \(\phi_m\) links every turn; no winding resistance; no leakage flux; no core losses; and a core so permeable that the current needed to magnetise it is negligible. Real power transformers come close: large units are typically over 99% efficient, and the ideal equations are good to within a few percent. Their losses are modelled in "Equivalent circuits, coupled coils, and air-core transformers".
The transformer emf equation
Let the core flux be sinusoidal, \(\phi_m = \Phi_m \sin\omega t\), where \(\Phi_m\) is its peak value. Faraday's law gives \(e_p = N_p\,d\phi_m/dt = \omega N_p\Phi_m\cos\omega t\), a sinusoid of peak value \(\omega N_p\Phi_m\). Dividing by \(\sqrt{2}\) for the rms value and using \(2\pi/\sqrt{2} \approx 4.44\):
Here \(E_p\) and \(E_s\) are rms volts, f is in hertz and \(\Phi_m\) is the peak flux in webers. The equation shows that for a given voltage and frequency, the winding sets the flux the core must carry.
The turns ratio
Divide the two emf equations and everything except the turns cancels:
The quantity a is the transformation ratio. Both windings see the same flux at every instant, so their voltages are in phase. In the ideal case \(E_p = V_p\), the applied voltage, and \(E_s = V_s\), the load voltage. When \(a > 1\) the secondary voltage is lower and the transformer is step-down; when \(a < 1\) it is step-up. Watch the definition: this course follows the common convention \(a = N_p/N_s\), but some books and datasheets quote \(N_s/N_p\) instead.
Worked example: sizing a small transformer
A transformer for 120 V at 60 Hz has a 400-turn primary and must give 24 V. Find the peak core flux, the peak flux density if the core cross-section is 10.0 cm², and the secondary turns. 1. Peak flux:
2. Flux density: \(B_m = \Phi_m/A\) with \(A = 1.00 \times 10^{-3}\,\text{m}^2\), so \(B_m = 1.13\,\text{T}\), a typical working level for silicon steel. 3. Turns ratio: \(a = 120/24 = 5\), so \(N_s = 400/5 = 80\) turns. 4. Check: \(4.44 \times 60 \times 80 \times 1.126\,\text{mWb}\) gives 24.0 V.
Currents follow the inverse ratio
When a load draws secondary current, the secondary ampere-turns \(N_s I_s\) try to change the core flux. The flux cannot change, because it is fixed by the applied voltage through the emf equation, so the primary draws extra current whose ampere-turns cancel the secondary's: \(N_pI_p = N_sI_s\). Hence
The same result follows from power balance: an ideal transformer stores and wastes nothing, so \(V_pI_p = V_sI_s\). So the high-voltage winding has many turns of thin wire, and the low-voltage winding fewer, heavier turns.
Worked example: a distribution transformer
A pole-mounted transformer steps 7200 V down to 240 V and supplies a 4.80 kW resistive water heater on its secondary. Find a, the secondary and primary currents, and the heater resistance. 1. \(a = 7200/240 = 30\). 2. Secondary current: \(I_s = P/V_s = 4800/240 = 20.0\,\text{A}\). 3. Primary current: \(I_p = I_s/a = 20.0/30 = 0.667\,\text{A}\). 4. Heater resistance: \(R = V_s/I_s = 240/20.0 = 12.0\,\Omega\). 5. Check power balance: \(V_pI_p = 7200 \times 0.667 = 4.80\,\text{kW}\), equal to the output, as an ideal transformer requires.
Why transformers need alternating current
Transformer action depends on a changing flux. Apply a steady dc voltage to the primary and the flux settles to a constant value, so the secondary voltage is zero once the switching transient dies away. Worse, the primary then has no back-emf to oppose the supply: its current is limited only by the small winding resistance, so it can overheat or burn out. Any changing voltage with no steady dc part, sinusoidal or not, does transform, which is why transformers also appear in switch-mode supplies. Frequency matters too: by the emf equation, the same voltage at a lower frequency demands more flux, a point picked up in "Nameplate data and transformer types".
High voltage for transmission
A line delivering power P at voltage V carries current \(I = P/V\), and its conductors waste \(P_\text{loss} = I^2R\). For the same power, raising V by a factor n cuts the current by n and the loss by \(n^2\). So the grid generates at a convenient voltage, steps up for the long journey and steps down near the customer. Higher voltage needs taller towers and longer insulators, so utilities balance loss against construction cost. Typical US transmission voltages run from about 115 kV to 765 kV. The interconnected grid must also match generation to demand every second: if demand outruns supply, the generators slow and the frequency sags below 60 Hz, so operators call on reserves to restore it.
Worked example: losses at two voltages
A wind farm sends 12.0 MW through a line whose conductors have a total resistance of 4.00 Ω. Compare the losses at 34.5 kV and 138 kV, treating the line as single-phase at unity power factor for simplicity. 1. At 34.5 kV: \(I = 12.0 \times 10^6/34{,}500 = 348\,\text{A}\), and \(P_\text{loss} = 347.8^2 \times 4.00 = 484\,\text{kW}\), about 4.0% of the power sent. 2. At 138 kV: \(I = 87.0\,\text{A}\), and \(P_\text{loss} = 86.96^2 \times 4.00 = 30.2\,\text{kW}\), about 0.25%. 3. Check: the voltage rose by a factor of 4, so the loss should fall by \(4^2 = 16\), and \(484/30.2 = 16.0\).
From power station to wall socket
Generators typically produce somewhere between about 10 kV and 25 kV. Step-up transformers at the station feed the transmission lines; substations step down to distribution voltages, commonly around 4 to 35 kV; and a final transformer near each building gives 120/240 V at 60 Hz in the US, or about 230 V at 50 Hz in much of the world. This chain is why ac won the "war of the currents" of the late 1880s and 1890s, when Thomas Edison backed dc against George Westinghouse and Nikola Tesla's ac; the Niagara Falls plant supplying Buffalo from about 1896 sealed the case. Today, high-voltage dc links, made practical by power electronics, serve very long lines and undersea cables. Every voltage here can kill: qualified people work on such equipment only when it is isolated and locked out.
Common mistakes to avoid
First, inverting the current ratio: currents scale by \(N_s/N_p\), the opposite of the voltages, so the high-voltage side carries the smaller current. Second, using peak voltage in the emf equation, or \(2\pi\) in place of 4.44; the equation links rms voltage to peak flux. Third, expecting a transformer to step up power; voltage rises only as current falls, and power out never exceeds power in. Fourth, forgetting that line loss depends on the square of the current, so doubling the voltage quarters the loss rather than halving it.
Key takeaways
An iron core makes k nearly 1. The emf equation E = 4.44fNΦm links rms voltage to peak flux. Voltages follow the turns, Vp/Vs = Np/Ns = a, and are in phase; a > 1 steps down and a < 1 steps up. Currents follow the inverse ratio, Ip/Is = 1/a, because the ampere-turns balance and power in equals power out. Transformers need a changing flux, so steady dc does not transform. Raising transmission voltage by a factor n cuts I²R loss by n², which is why grids step up for transmission and step down for use.
Flashcards
Flashcard
k = 1, no winding resistance, no leakage, no core loss, negligible magnetising current
Test your understanding
Question 1 of 5
A transformer steps 240 V down to 12 V. Its primary has 600 turns. How many turns does the secondary need?
Question 2 of 5
An ideal step-down transformer has a = 10, and its load draws 15 A from the secondary. What current flows in the primary?
Question 3 of 5
A 500-turn primary is connected to 230 V rms at 50 Hz. What is the peak flux in the core?
Question 4 of 5
A line delivers a fixed power. Its voltage is tripled while the conductors stay the same. What happens to the I²R loss in the line?
Question 5 of 5
A steady 12 V dc supply is connected to the primary of a small transformer. What happens once the switch-on transient has passed?