Electrical Engineering › Section L · Power (ac) and resonance › Topic L.2

The power triangle and total P, Q, and S

Real, reactive and apparent power fit together as the sides of a right triangle. Draw it once and you can total the power of a whole building, find its power factor and work out the supply current without solving the circuit.

Three powers on one diagram

The previous topic, "Resistive, inductive, and capacitive power", defined real power \(P = VI\cos\theta\), reactive power \(Q = VI\sin\theta\) and apparent power \(S = VI\). Put \(P\) along the real axis and \(Q\) along the imaginary axis, and the apparent power becomes a complex number, the complex power, in rectangular form:

\mathbf{S} = P + jQ

Its magnitude is \(S\) and its angle is the power-factor angle \(\theta\). For an inductive load \(Q\) is positive and the triangle points up; for a capacitive load \(Q\) is negative and it points down. Because \(Q\) sits at \(90^\circ\) to \(P\), reactive power is also called quadrature power.

Reading the triangle

Since the sides are at right angles, Pythagoras and basic trigonometry link them:

S^2 = P^2 + Q^2
\cos\theta = \frac{P}{S},\quad \tan\theta = \frac{Q}{P}

Any two of \(P\), \(Q\), \(S\) and \(\theta\) fix the other two. A motor drawing 4.0 kW at a power factor of 0.80 lagging has \(S = 4.0/0.80 = 5.0\) kVA and \(Q = +3.0\) kVAR. Always state the power factor with its direction: lagging (current behind voltage, \(Q > 0\), inductive) or leading (current ahead, \(Q < 0\), capacitive). A bare "0.8" is ambiguous.

Where the triangle comes from

In a series circuit every element carries the same current \(I\). Take the impedance triangle of a series R-L-C circuit, with sides \(R\), \(X_L - X_C\) and \(|Z|\), and multiply each side by \(I^2\). The sides become \(I^2R = P\), \(I^2(X_L - X_C) = Q\) and \(I^2|Z| = S\). So the power triangle is the impedance triangle scaled by \(I^2\), with the same angle. This also shows why reactive powers subtract: the inductor's \(I^2X_L\) and the capacitor's \(I^2X_C\) point in opposite directions, so the net reactive power is their difference.

Complex power from phasors

With rms phasors \(\mathbf{V}\) and \(\mathbf{I}\), complex power is

\mathbf{S} = \mathbf{V}\mathbf{I}^*

where \(\mathbf{I}^*\) denotes the conjugate of the current phasor (same magnitude, angle negated). The conjugate makes the angle of \(\mathbf{S}\) equal to the voltage angle minus the current angle, which is \(\theta\). For example, \(\mathbf{V} = 120\angle 0^\circ\) V across \(Z = 8 + j6\,\Omega\) gives \(\mathbf{I} = 12\angle{-36.9^\circ}\) A. Then \(\mathbf{S} = (120)(12)\angle 36.9^\circ = 1152 + j864\) VA. Check: \(I^2R = 144 \times 8 = 1152\) W and \(I^2X = 144 \times 6 = 864\) VAR.

Worked example: a series R-L-C circuit

A 120 V, 60 Hz source drives \(R = 33\,\Omega\), \(X_L = 68\,\Omega\) and \(X_C = 22\,\Omega\) in series. 1. \(Z = 33 + j(68 - 22) = 33 + j46\,\Omega\), which in polar form is \(56.6\angle 54.3^\circ\,\Omega\). 2. \(I = 120/56.6 = 2.12\) A, lagging by \(54.3^\circ\). 3. \(P = I^2R = 148\) W. 4. \(Q_L = I^2X_L = +306\) VAR and \(Q_C = -I^2X_C = -98.8\) VAR, so \(Q = +207\) VAR. 5. \(S = \sqrt{148^2 + 207^2} = 254\) VA. 6. Check: \(VI = 120 \times 2.12 = 254\) VA, and \(F_p = P/S = 0.583\) lagging, equal to \(\cos 54.3^\circ\).

Totals for a whole system

For any network, however its loads are connected: 1. find \(P\) and \(Q\) for each load or branch; 2. add the real powers, \(P_T = \sum P\); 3. add the reactive powers with their signs, inductive positive and capacitive negative, to get \(Q_T\); 4. find \(S_T = \sqrt{P_T^2 + Q_T^2}\); 5. the overall power factor is \(P_T/S_T\), lagging if \(Q_T > 0\) and leading if \(Q_T < 0\). Two points matter. The apparent powers of the loads do not add, because they point in different directions. And the arrangement does not matter: series, parallel or a mixture, energy is conserved, so \(P\) and \(Q\) each simply add.

Worked example: three loads on one supply

A 240 V, 60 Hz supply feeds, in parallel, lighting of 1.2 kW (\(F_p = 1\)), a motor of 3.0 kVA at 0.75 lagging, and an electronic load of 1.5 kVA at 0.90 leading. 1. Lighting: \(P = 1.20\) kW, \(Q = 0\). 2. Motor: \(P = 3.0 \times 0.75 = 2.25\) kW, \(Q = 3.0\sin(\cos^{-1}0.75) = +1.98\) kVAR. 3. Electronic load: \(P = 1.35\) kW, \(Q = -1.5\sin(\cos^{-1}0.90) = -0.654\) kVAR. 4. \(P_T = 4.80\) kW and \(Q_T = +1.33\) kVAR. 5. \(S_T = \sqrt{4.80^2 + 1.33^2} = 4.98\) kVA, not the 5.7 kVA that adding the ratings would suggest. 6. \(F_p = 4.80/4.98 = 0.964\) lagging.

The supply current

Once \(S_T\) is known, the supply current follows from \(I = S_T/V\). In the three-load example, \(I = 4981/240 = 20.8\) A. Its angle comes from the power factor: \(\theta = \cos^{-1}0.964 = 15.5^\circ\), and because the power factor is lagging the current lags the voltage. Taking the supply voltage as the reference, \(240\angle 0^\circ\) V, the current in polar form is \(\mathbf{I} = 20.8\angle{-15.5^\circ}\) A. For a leading power factor the angle would be positive. No mesh or nodal analysis was needed: the power totals alone gave the current.

From a rating to an impedance

The triangle also runs backwards. A device is rated 2.0 kVA at 240 V with a power factor of 0.85 lagging. 1. \(I = 2000/240 = 8.33\) A. 2. \(|Z| = V/I = 28.8\,\Omega\). 3. \(\theta = \cos^{-1}0.85 = 31.8^\circ\), positive because lagging. 4. In rectangular form, \(Z = 28.8\angle 31.8^\circ = 24.5 + j15.2\,\Omega\). So the device behaves like 24.5 Ω of resistance in series with 15.2 Ω of inductive reactance. Check: \(I^2R = 8.33^2 \times 24.5 = 1.70\) kW, which is \(2.0 \times 0.85\) kW.

Common mistakes to avoid

First, adding apparent powers: \(S_T\) must come from \(P_T\) and \(Q_T\), never from \(\sum S\). Second, adding all reactive powers as positive: capacitive VAR subtract from inductive VAR. Third, forgetting the conjugate: \(\mathbf{V}\mathbf{I}\) without the star gives the wrong angle, and so the wrong sign of \(Q\). Fourth, quoting a power factor without "lagging" or "leading". Fifth, thinking a series connection needs a different method from a parallel one: the totals rule works for any arrangement.

Key takeaways

Complex power is \(\mathbf{S} = P + jQ = \mathbf{V}\mathbf{I}^*\), with \(S^2 = P^2 + Q^2\) and power-factor angle \(\theta\), where \(\cos\theta = P/S\) and \(\tan\theta = Q/P\). Inductive \(Q\) is positive (lagging), capacitive \(Q\) negative (leading). The power triangle is the impedance triangle scaled by \(I^2\). For a whole system, add the \(P\) values, add the signed \(Q\) values, then find \(S_T\) and \(F_p = P_T/S_T\), whatever the connection. The supply current is \(S_T/V\), lagging or leading by \(\theta\).

Flashcards

Flashcard

Complex power

S = P + jQ, in volt-amperes

Real part watts, imaginary part VAR.

Test your understanding

Question 1 of 5

A load absorbs 600 W and 800 VAR (inductive). What are its apparent power and power factor?

Question 2 of 5

Two loads share a supply: 2.0 kW at 0.8 lagging and 1.0 kW at 0.6 leading. What is the total reactive power?

Question 3 of 5

A 120∠0° V source drives a current of 5∠−30° A. What is the complex power S = V I*?

Question 4 of 5

Three loads have apparent powers of 1.0 kVA, 2.0 kVA and 3.0 kVA. Which statement about the total apparent power is true?

Question 5 of 5

A device is rated 5.0 kVA at 250 V with a power factor of 0.8 lagging. What is its equivalent series impedance?