Electrical Engineering › Section M · Transformers and polyphase systems › Topic M.8

Delta-connected systems

Connect three coils or three loads end to end in a closed triangle and you have a delta. Here the voltages are the simple part, since phase and line voltages are equal, while the currents pick up the factor of √3 and the 30° shift.

Connecting the coils in delta

Instead of joining the three coil ends N at a neutral, a generator's coils can be joined in series around a closed loop, the end of each to the start of the next. The three junctions become the terminals A, B and C, and lines run from them to the load. Drawn as a triangle, this is the delta (Δ) connection. There is no neutral point, so a plain Δ system is three-phase three-wire and offers only one voltage. Loads can be connected the same way, three impedances \(Z_{ab}\), \(Z_{bc}\) and \(Z_{ca}\) forming a triangle between the lines. The phase sequence throughout is ABC, as in "Y-connected generators and loads".

Voltages: phase equals line

Each coil of a Δ generator is connected directly between two lines, so the voltage across a coil is a line voltage:

E_L = E_\phi

For the same reason, each branch of a Δ load sees the full line voltage, whatever is feeding it. Because a Δ has no neutral to measure from, its phase sequence is described by the line voltages. With sequence ABC and \(\mathbf{E}_{AB}\) chosen as reference, \(\mathbf{E}_{AB} = E_L\angle 0^\circ\), \(\mathbf{E}_{BC} = E_L\angle -120^\circ\) and \(\mathbf{E}_{CA} = E_L\angle 120^\circ\). When drawing them, keep the subscript order consistent: AB, BC, CA, with first and second subscripts both running A, B, C.

Currents: line current from two phases

At each corner of a Δ, one line meets two branches. Take \(\mathbf{I}_{ab}\) as flowing from a to b and \(\mathbf{I}_{ca}\) from c to a. At corner a of a Δ load, the line current plus the current arriving from branch ca must leave through branch ab, so Kirchhoff's current law gives \(\mathbf{I}_{Aa} = \mathbf{I}_{ab} - \mathbf{I}_{ca}\). For a balanced load with sequence ABC, \(\mathbf{I}_{ca}\) is \(\mathbf{I}_{ab}\) shifted by +120°, so \(\mathbf{I}_{Aa} = \mathbf{I}_{ab}(1 - 1\angle 120^\circ)\). In rectangular form \(1 - 1\angle 120^\circ = 1.5 - j0.866\), which is \(1.732\angle -30^\circ\). Hence

I_L = \sqrt{3}\,I_\phi

with each line current lagging its phase current by 30°. This mirrors the Y result, with currents in place of voltages.

Why most generators are Y-connected

A closed Δ loop carries the sum of the three coil voltages around itself. For a perfectly balanced, perfectly sinusoidal generator that sum is zero, so no current circulates. Real machines are never perfect. Any small imbalance, and especially any third-harmonic content in the coil voltages, which is in phase in all three coils and so does not cancel, drives a current around the loop even with no load attached, heating the windings for nothing. For this reason, among others, large generators are almost always Y-connected. The Δ connection remains common for transformer windings and for loads such as three-phase motors and heaters.

The Δ-Δ system

In a Δ-Δ system, each load branch is connected across the same pair of lines as one generator coil, so \(\mathbf{V}_{ab} = \mathbf{E}_{AB}\), \(\mathbf{V}_{bc} = \mathbf{E}_{BC}\) and \(\mathbf{V}_{ca} = \mathbf{E}_{CA}\). Each branch current then follows from Ohm's law: \(\mathbf{I}_{ab} = \mathbf{V}_{ab}/Z_{ab}\), and so on. The line currents come from the corner differences, or, for a balanced load, from \(\sqrt{3}\) and the 30° lag. Because each load branch has its own pair of lines, an unbalanced Δ load is also easy to solve: compute each branch current separately, then take the corner differences. No neutral current needs to be found.

Worked example: a balanced Δ-Δ load

A 240 V Δ generator, sequence ABC, feeds a Δ load of \(12 + j16 = 20\angle 53.13^\circ\,\Omega\) per phase. Take \(\mathbf{E}_{AB} = 240\angle 0^\circ\,\text{V}\). 1. Branch current: \(\mathbf{I}_{ab} = 240\angle 0^\circ/20\angle 53.13^\circ\), which is \(12.0\angle -53.13^\circ\,\text{A}\). 2. Similarly \(\mathbf{I}_{bc} = 12.0\angle -173.13^\circ\) and \(\mathbf{I}_{ca} = 12.0\angle 66.87^\circ\) amperes. 3. Line current: \(\mathbf{I}_{Aa} = \mathbf{I}_{ab} - \mathbf{I}_{ca}\), with \(\mathbf{I}_{ab} = 7.20 - j9.60\) and \(\mathbf{I}_{ca} = 4.71 + j11.04\), giving \(2.49 - j20.64\,\text{A}\). 4. Polar: \(20.8\angle -83.13^\circ\,\text{A}\), which is \(\sqrt{3} \times 12.0 = 20.8\) at \(-53.13^\circ - 30^\circ\), as predicted. 5. The three line currents are 120° apart and sum to zero.

The Δ-Y system

A Δ generator can also feed a Y load. Now each load phase connects a line to the load's own neutral point n, which has no conductor back to the generator. For a balanced Y load, the results of "Y-connected generators and loads" apply in reverse: each load phase voltage is the line voltage divided by \(\sqrt{3}\), and it lags its line voltage by 30°. So with \(\mathbf{E}_{AB}\) at 0°, \(\mathbf{V}_{an} = (E_L/\sqrt{3})\angle -30^\circ\). The phase currents, which are also the line currents in a Y, follow from Ohm's law. The Δ-Y combination is common in practice: many distribution transformers have a Δ primary and a Y secondary.

Worked example: a balanced Δ-Y load

A 208 V Δ generator, sequence ABC, with \(\mathbf{E}_{AB} = 208\angle 0^\circ\,\text{V}\), feeds a balanced Y load of \(9 + j12 = 15\angle 53.13^\circ\,\Omega\) per phase. 1. Load phase voltage: \(\mathbf{V}_{an} = (208/\sqrt{3})\angle -30^\circ\), which is \(120.1\angle -30^\circ\,\text{V}\). 2. Line current: \(\mathbf{I}_{Aa} = \mathbf{V}_{an}/Z_\phi\), which is \(8.01\angle -83.13^\circ\,\text{A}\). 3. The other two: \(8.01\angle 156.87^\circ\) and \(8.01\angle 36.87^\circ\) amperes. 4. Check: with \(\mathbf{V}_{bn} = 120.1\angle -150^\circ\,\text{V}\), the difference \(\mathbf{V}_{an} - \mathbf{V}_{bn}\) is \(208\angle 0^\circ\,\text{V}\), equal to \(\mathbf{E}_{AB}\), as it must be.

One phase is enough when balanced

Recall from "Bridge networks and delta-Y conversions (ac)" that three equal Δ impedances are equivalent to three equal Y impedances of one third the size: \(Z_Y = Z_\Delta/3\). That gives a shortcut for any balanced system. Replace every Δ by its Y equivalent, solve one phase from line to neutral with the phase voltage \(V_L/\sqrt{3}\), and generate the other two phases by shifting −120° and +120°. For the Δ-Δ example, \(Z_Y = (12 + j16)/3 = 4 + j5.33\,\Omega\), and dividing \(138.6\angle -30^\circ\,\text{V}\) by \(6.67\angle 53.13^\circ\,\Omega\) gives \(20.8\angle -83.13^\circ\,\text{A}\), the same line current as before.

Common mistakes to avoid

First, applying \(\sqrt{3}\) to Δ voltages; in a Δ, phase and line voltages are equal, and only the currents differ. Second, getting the 30° the wrong way: with sequence ABC, a Δ line current lags its phase current by 30°, while a Y line voltage leads its phase voltage by 30°. Third, writing \(\mathbf{I}_{Aa} = \mathbf{I}_{ab} + \mathbf{I}_{ca}\); the corner current is a difference, set by the reference directions. Fourth, using \(Z_Y = 3Z_\Delta\) instead of \(Z_\Delta/3\). Fifth, giving a Δ load a phase voltage of \(V_L/\sqrt{3}\).

Key takeaways

In a Δ, coils or loads form a closed triangle between the lines; there is no neutral, so the system is three-wire with one voltage. Phase voltage equals line voltage. Line current is the difference of two phase currents, I_Aa = I_ab − I_ca; when balanced with sequence ABC, I_L = √3 I_φ, lagging the phase current by 30°. Large generators avoid Δ because imbalance and third harmonics drive circulating current. In Δ-Δ each branch sees the line voltage; in Δ-Y each load phase gets V_L/√3, lagging its line voltage by 30°. For balanced systems, convert with Z_Y = Z_Δ/3 and solve one phase.

Flashcards

Flashcard

Delta (Δ) connection

Coils or loads joined end to end in a closed triangle

Lines leave from the three corners.

Test your understanding

Question 1 of 5

A balanced Δ load has 18 A flowing in each branch. What is the line current?

Question 2 of 5

A balanced Δ load is connected to a 480 V three-phase supply. What voltage appears across each load branch?

Question 3 of 5

In a balanced Δ load with sequence ABC, I_ab = 10∠−20° A. What is the line current I_Aa?

Question 4 of 5

A balanced Δ load of 27 + j36 Ω per branch is replaced by its Y equivalent for per-phase analysis. What is the Y impedance per phase?

Question 5 of 5

Why are large generators rarely connected in Δ?