Electrical Engineering › Section M · Transformers and polyphase systems › Topic M.7
Y-connected generators and loads
Join one end of each generator coil at a common point and you have a Y connection, the most common arrangement in power distribution. It offers two voltages from one system, such as 120 V and 208 V, linked by a factor of √3 and a 30° shift.
Connecting the coils in Y
The three coils of "Polyphase systems and the three-phase generator" each have ends labelled A, B, C and N. Join the three N ends together and the result, drawn like the letter Y, is a Y-connected generator, also called a star connection. The junction is the neutral point. The three conductors that carry power out to the load are the lines. If only the three lines go to the load, the system is three-phase three-wire; if a fourth conductor joins the neutral to the load, it is three-phase four-wire. Throughout, the phase sequence is ABC: \(\mathbf{E}_{AN} = E_\phi\angle 0^\circ\), \(\mathbf{E}_{BN} = E_\phi\angle -120^\circ\) and \(\mathbf{E}_{CN} = E_\phi\angle 120^\circ\), all rms phasors.
Phase quantities and line quantities
A phase quantity belongs to one coil or one load branch: the phase voltage across it and the phase current through it, written with subscript \(\phi\). A line quantity belongs to the lines: the line current in a line and the line voltage between two lines, written with subscript L. In a Y connection each line is in series with exactly one phase, so the line current is the phase current:
Double subscripts give voltage directions: \(\mathbf{E}_{AB}\) is the voltage of point A measured relative to point B. So \(\mathbf{E}_{AN}\) is a phase voltage, from line A to neutral, and \(\mathbf{E}_{AB}\) is a line voltage, from line A to line B.
Line voltage from phase voltages
Kirchhoff's voltage law along the path from A through N to B gives \(\mathbf{E}_{AB} = \mathbf{E}_{AN} + \mathbf{E}_{NB} = \mathbf{E}_{AN} - \mathbf{E}_{BN}\). For a balanced generator with sequence ABC, subtracting phasors 120° apart gives a result \(\sqrt{3}\) times as long and rotated 30° ahead:
In words: in a balanced Y with sequence ABC, each line voltage is \(\sqrt{3}\) times the phase voltage and leads its phase voltage by 30°. The other two follow the same pattern: \(\mathbf{E}_{BC}\) leads \(\mathbf{E}_{BN}\) by 30° and \(\mathbf{E}_{CA}\) leads \(\mathbf{E}_{CN}\) by 30°. Like the phase voltages, the three line voltages sum to zero.
Worked example: line voltages of a 120 V Y
A balanced Y generator, sequence ABC, has 120 V phases. Find \(\mathbf{E}_{AB}\) and the other line voltages. 1. Rectangular form: \(\mathbf{E}_{AN} = 120\) and \(\mathbf{E}_{BN} = -60 - j103.9\,\text{V}\). 2. Subtract: \(\mathbf{E}_{AB} = 120 - (-60 - j103.9)\), which is \(180 + j103.9\,\text{V}\). 3. Polar form: \(\sqrt{180^2 + 103.9^2} = 207.8\,\text{V}\) at \(\tan^{-1}(103.9/180) = 30.0^\circ\), so \(\mathbf{E}_{AB} = 208\angle 30^\circ\,\text{V}\). 4. Check: \(\sqrt{3} \times 120 = 207.8\). 5. Rotating by −120° each time: \(\mathbf{E}_{BC} = 208\angle -90^\circ\) and \(\mathbf{E}_{CA} = 208\angle 150^\circ\) volts.
Two voltages from one system
A four-wire Y supply offers two voltages: phase voltage between any line and neutral, and line voltage between any two lines. US commercial buildings commonly use 120/208 V, with lights and outlets on 120 V and larger loads on 208 V. Larger buildings often use 277/480 V, with fluorescent and LED lighting on 277 V and motors on 480 V. Europe's low-voltage distribution is 230/400 V: \(\sqrt{3} \times 230 = 398\), rounded to 400 V. The phase voltage is quoted first. Note that 208 V is not the same as the 240 V of a split-phase home service from "Nameplate data and transformer types".
Phase sequence in practice
Picture the phasor diagram spinning anticlockwise past a fixed reference line: the sequence is the order in which the phasors cross it. With A at 0°, B at −120° and C at 120°, they pass in the order A, B, C; since the cycle repeats, BCA and CAB name the same sequence. The line voltages show the same sequence, read from their first subscripts: \(\mathbf{E}_{AB}\), then \(\mathbf{E}_{BC}\), then \(\mathbf{E}_{CA}\). To draw a diagram from a given sequence, place any one voltage on the reference axis and set the others 120° apart in the stated order. Electricians check the sequence on site with a phase-rotation meter before connecting motors, because the wrong order reverses them.
The Y-Y system
Connect a Y load, with phase impedances \(Z_{an}\), \(Z_{bn}\) and \(Z_{cn}\), to a four-wire Y generator. Each load phase sits directly between a line and the neutral, so its voltage is the generator's phase voltage and its current is \(I_\phi = V_\phi/Z_\phi\). By Kirchhoff's current law at the load's neutral point, the neutral carries \(\mathbf{I}_N =\mathbf{I}_{an} + \mathbf{I}_{bn} + \mathbf{I}_{cn}\). A load is balanced when all three impedances are equal in both magnitude and angle. Then the three currents are equal in size and 120° apart, they sum to zero, and \(\mathbf{I}_N =0\): the neutral could be removed. Real buildings keep it, because single-phase loads switching on and off never stay perfectly balanced.
Worked example: a balanced Y-Y load
The 120 V generator above supplies a four-wire Y load of \(8 + j6\,\Omega\) per phase, in rectangular form. Find the line currents and the neutral current. 1. Polar impedance: \(Z_\phi = 10\angle 36.87^\circ\,\Omega\). 2. \(\mathbf{I}_{Aa} = 120\angle 0^\circ/10\angle 36.87^\circ\), which is \(12\angle -36.87^\circ\,\text{A}\). 3. Likewise \(\mathbf{I}_{Bb} = 12\angle -156.87^\circ\) and \(\mathbf{I}_{Cc} = 12\angle 83.13^\circ\) amperes. 4. Rectangular: \(9.60 - j7.20\), \(-11.04 - j4.71\) and \(1.44 + j11.91\). 5. Neutral: the real parts sum to 0 and the imaginary parts to 0, so \(\mathbf{I}_N =0\), as a balanced load requires. Each line current equals its phase current, 12 A.
The Y-Δ system
A three-phase load can also be connected in delta (Δ), with its three impedances forming a closed triangle between the lines. A Δ load has no neutral point, so a Y-Δ system is always three-wire. Each load impedance is connected from line to line, so its voltage is a line voltage of the generator: \(\mathbf{V}_{ab} = \mathbf{E}_{AB}\), and so on. Each line now feeds two load branches, and its current is the phasor difference of two phase currents: \(\mathbf{I}_{Aa} = \mathbf{I}_{ab} - \mathbf{I}_{ca}\). For a balanced load with sequence ABC this gives line currents \(\sqrt{3}\) times the phase currents and lagging them by 30°, a result derived in "Delta-connected systems".
Worked example: a balanced Y-Δ load
A 277/480 V Y generator, sequence ABC, feeds a Δ load of \(24 + j18 = 30\angle 36.87^\circ\,\Omega\) per phase. 1. Load voltage: \(\mathbf{V}_{ab} = \mathbf{E}_{AB} = 480\angle 30^\circ\,\text{V}\). 2. Phase current: \(\mathbf{I}_{ab} = 480\angle 30^\circ/30\angle 36.87^\circ\), which is \(16.0\angle -6.87^\circ\,\text{A}\). 3. Line current: \(I_L = \sqrt{3} \times 16.0 = 27.7\,\text{A}\), so \(\mathbf{I}_{Aa} = 27.7\angle -36.87^\circ\,\text{A}\). 4. Check with KCL: \(\mathbf{I}_{ab} = 15.89 - j1.91\) and \(\mathbf{I}_{ca} = 16.0\angle 113.13^\circ\), which is \(-6.29 + j14.71\). Their difference is \(22.17 - j16.63\,\text{A}\) to rounding, or \(27.7\angle -36.87^\circ\,\text{A}\).
Common mistakes to avoid
First, applying \(\sqrt{3}\) to Y currents; in a Y, line current equals phase current, and only the voltages differ. Second, forgetting the 30° shift and writing \(\mathbf{E}_{AB}\) at 0° when \(\mathbf{E}_{AN}\) is the reference. Third, reversing subscripts: \(\mathbf{E}_{BA} = -\mathbf{E}_{AB}\), which is 180° away. Fourth, calling a load balanced when the impedance magnitudes match but the angles differ; both must match.
Key takeaways
In a Y connection the coil ends N meet at the neutral; three-wire systems omit the neutral conductor, four-wire systems include it. Line current equals phase current. With sequence ABC, each line voltage is √3 times the phase voltage and leads it by 30°, so E_AB = √3 E_φ ∠30° when E_AN is at 0°. Common supplies are 120/208 V, 277/480 V and 230/400 V. In a Y-Y system each load phase gets the phase voltage, and a balanced load makes the neutral current zero. In a Y-Δ system each load branch gets the line voltage, and the line currents are √3 times the phase currents.
Flashcards
Flashcard
The three N ends joined at a common neutral point
Test your understanding
Question 1 of 5
A balanced Y generator has a phase voltage of 277 V rms. What is its line voltage?
Question 2 of 5
In a balanced Y system with sequence ABC, E_AN = 120∠0° V. Which is E_AB?
Question 3 of 5
A balanced Y load of 6 + j8 Ω per phase is fed with 120 V per phase. What is the magnitude of each line current?
Question 4 of 5
A four-wire Y-Y system has equal impedance magnitudes in all three load phases, but one phase is resistive and the other two are inductive. What can you say about the neutral current?
Question 5 of 5
A balanced Δ load is fed from a 120/208 V Y generator. Each Δ branch has an impedance of 20.8 Ω. What is the line current?