Electrical Engineering › Section Z · AC motors › Topic Z.4

Polyphase, wound-rotor, and single-phase induction motors

The induction motor has no brushes, no magnets and no electrical connection to its rotor, yet it drives most of the world's pumps, fans and machines. Its secret is a rotating field and a rotor that always runs a little behind it.

Industry's workhorse

Most industrial motors above about a kilowatt are three-phase induction motors, Tesla's invention of the late 1880s. The stator is a stack of slotted laminations carrying a distributed three-phase winding. The usual rotor, the squirrel cage, is a laminated cylinder with aluminium or copper bars in its slots, joined at each end by a shorting ring; the bars are often skewed slightly to smooth the torque. Nothing connects the rotor to the supply. Like a transformer secondary, it gets its current by induction alone, so the machine is rugged, cheap and nearly maintenance-free.

The rotating magnetic field

Place three windings 120° apart round the stator and feed them three-phase currents. Each winding alone makes a field that pulses back and forth along its own axis. Add the three as vectors at any instant and the result has constant strength, 1.5 times the peak field of one winding, and points in a direction that turns steadily, one pole pair per cycle:

n_s = \frac{120f}{P}

P being the total number of poles. Tesla's original two-phase scheme, two windings 90° apart with currents 90° apart, works too. Swapping any two of the three supply leads reverses the phase sequence, and so reverses the motor.

Torque from slip

As the field sweeps past the rotor bars it induces voltages in them, by "Faraday's and Lenz's laws", and currents flow round the cage. Those currents feel a force in the field that drags the rotor after it. The rotor can never quite catch up: at synchronous speed the bars would cut no flux, carry no current and make no torque. The fractional shortfall is the slip,

s = \frac{n_s - n}{n_s}

which at full load is typically a few percent. Rotor currents alternate at the slip frequency \(f_r = sf\), the line frequency at standstill but a hertz or two when running. More load brings more slip, rotor current and torque.

Worked example: slip and power flow

A 4-pole, 60 Hz motor runs at 1,746 rpm, with 20.0 kW crossing the air gap to the rotor. 1. \(n_s = 120 \times 60/4 = 1800\,\text{rpm}\). 2. \(s = (1800 - 1746)/1800 = 0.030\), or 3.0%. 3. Rotor frequency: \(0.030 \times 60 = 1.8\,\text{Hz}\). 4. A standard result of the motor's equivalent circuit splits the air-gap power: a fraction \(s\) is rotor copper loss, \(0.030 \times 20.0 = 0.600\,\text{kW}\), and the rest, \(19.4\,\text{kW}\), becomes mechanical power. 5. Torque: \(19{,}400/(2\pi \times 1746/60) = 106\,\text{N}\,\text{m}\), the same as \(20{,}000/(2\pi \times 1800/60)\). High slip therefore means a hot rotor.

The torque-speed curve

At standstill the motor produces its locked-rotor torque while drawing a locked-rotor current commonly five to eight times full-load current, much as a transformer with a shorted secondary would. As it accelerates, torque may dip to a pull-up value, then rises to a peak, the breakdown torque, often two to three times full-load torque, before falling steeply to zero near synchronous speed. Normal running sits on that steep part, so speed barely varies with load; a load above breakdown torque stalls the motor. NEMA Design B is the general-purpose motor, Design C gives high starting torque, and Design D very high starting torque with slip of 5% or more.

Power factor, efficiency and generating

An induction motor always draws lagging current, because its field is magnetised from the supply. Near full load a large motor may reach a power factor of about 0.85 to 0.9 and an efficiency of 95% or more; lightly loaded, the magnetising current dominates and the power factor falls very low, though efficiency stays near its best down to about half load. Drive the rotor faster than \(n_s\) and the slip turns negative: the machine becomes an induction generator, feeding real power back. It still needs reactive power from the grid, or from capacitors, to set up its field, and early fixed-speed wind turbines used exactly this.

Starting and speed control

Small motors are switched straight onto the line. For large ones the starting current would make the supply sag, so they use reduced-voltage starting: an autotransformer, a solid-state soft starter, or a star-delta starter, which connects a delta-wound motor in Y while starting so that each winding sees \(1/\sqrt{3}\) of the line voltage. Torque varies roughly with the square of voltage, so starting torque falls too. Speed can be changed in steps with pole-changing windings, 4 poles to 8 for example, or smoothly with an inverter drive, covered in "Pulse-width modulation, DC motor drives, inverters, and AC motor drives", which varies the frequency and keeps the ratio of voltage to frequency roughly constant to hold the flux steady.

Worked example: starting and drive settings

A 460 V, 60 Hz, 4-pole motor, normally delta-connected, draws 6.0 times full-load current when started direct on line. 1. Star-delta start: each winding sees \(1/\sqrt{3}\) of its voltage, so its current falls by \(1/\sqrt{3}\), and the line current, no longer multiplied by \(\sqrt{3}\) as in a delta, falls to one third: \(6.0/3 = 2.0\) times full-load current. 2. Starting torque falls to one third too, since \((1/\sqrt{3})^2 = 1/3\). 3. On an inverter at 40 Hz with constant volts per hertz: \(V = 460 \times 40/60 = 307\,\text{V}\). 4. New synchronous speed: \(120 \times 40/4 = 1200\,\text{rpm}\), and the rotor runs a little below it.

Wound-rotor motors

A wound-rotor motor replaces the cage with a three-phase rotor winding brought out through slip rings and brushes to external resistors. Adding rotor resistance lowers the starting current and moves the breakdown torque to a higher slip, a lower speed, without changing its size; enough resistance puts the peak at standstill, giving very high starting torque for heavy, high-inertia loads. The resistance is cut out as the motor speeds up; leaving some in lowers the speed, wastefully. Modern wind turbines use a doubly-fed induction generator: a converter, rated at only about 30% of the machine's power, feeds the rotor, allowing speeds about 30% either side of synchronous.

Single-phase induction motors

One winding on single-phase ac makes a field that pulses but does not rotate. It can be pictured as two equal fields rotating in opposite directions; at standstill their torques cancel, so there is no starting torque, but once the rotor turns either way the forward field wins and it runs. Starting needs a second, auxiliary winding whose current is shifted in phase. A split-phase motor uses a high-resistance auxiliary winding, switched out by a centrifugal switch at about three quarters of synchronous speed. A capacitor-start motor puts a capacitor in that winding for a stronger start, as compressors need; a permanent-split capacitor motor keeps a small capacitor in circuit permanently, as many fans do.

Common mistakes to avoid

First, expecting an induction motor to reach synchronous speed; with zero slip there is no torque. Second, using the line frequency for the rotor current; it is \(sf\). Third, thinking more rotor resistance raises the breakdown torque; it moves the peak to a higher slip but keeps its size. Fourth, believing a single-phase motor's main winding can start it; it needs an auxiliary winding. Fifth, lowering an inverter's frequency without lowering its voltage; the flux rises and the core saturates.

Key takeaways

Three-phase stator currents make a field of constant strength rotating at n_s = 120f/P. It induces currents in the cage rotor, which runs with slip s = (n_s − n)/n_s, typically a few percent, and rotor frequency sf. Of the air-gap power, a fraction s is rotor copper loss and 1 − s becomes mechanical. Star-delta starting cuts starting current to a third; inverters vary speed at constant V/f. Wound-rotor motors use rotor resistance for strong starting. Single-phase motors need an auxiliary winding, split-phase or capacitor, to start.

Flashcards

Flashcard

Squirrel cage

Rotor bars shorted by end rings, embedded in laminated steel

No electrical connection to the supply.

Test your understanding

Question 1 of 5

A 6-pole induction motor on a 50 Hz supply runs at 960 rpm. What are its slip and its rotor frequency?

Question 2 of 5

An induction motor receives 10 kW across its air gap and runs at 4.0% slip. How much of that power is lost as heat in the rotor?

Question 3 of 5

A delta-connected induction motor draws 7.2 times full-load current when started direct on line. What line current does a star-delta starter give at the moment of starting?

Question 4 of 5

Extra resistance is added in series with the rotor of a wound-rotor induction motor. What happens to its breakdown torque?

Question 5 of 5

A single-phase induction motor's auxiliary winding has been disconnected by a fault. What happens when power is applied to the stationary motor?