Electrical Engineering › Section B · Resistance, Ohm's law, power, and energy › Topic B.1

Resistance of wires and wire tables

Every wire resists current a little, and that small resistance decides how hot a cable runs and how much voltage is lost along it. This topic shows how material, length and thickness set a conductor's resistance, in SI units, in the circular-mil units of US wire tables, and for thin films.

What resistance is

As free electrons drift through a conductor, they keep colliding with the vibrating ions of the lattice and with impurities. Those collisions oppose the flow of charge and turn electrical energy into heat. The opposition is called resistance, symbol \(R\), measured in ohms (Ω). For a uniform conductor at a fixed temperature, four things set its value: the material, the length, the cross-sectional area and the temperature. This topic deals with the first three at a fixed temperature of 20 °C; "Temperature effects and superconductors" deals with the fourth.

The resistance formula

A longer path means more collisions, so resistance is proportional to length. A wider path offers more routes side by side, so resistance is inversely proportional to cross-sectional area. The material enters through its resistivity \(\rho\) (rho):

R = \frac{\rho\,l}{A}

In SI, \(l\) is in metres, \(A\) in square metres and \(\rho\) in ohm-metres (Ω·m). Resistivities at 20 °C:

\begin{array}{ll} \text{silver} & 1.59 \times 10^{-8} \\ \text{copper} & 1.72 \times 10^{-8} \\ \text{gold} & 2.44 \times 10^{-8} \\ \text{aluminium} & 2.82 \times 10^{-8} \\ \text{nichrome} & 1.10 \times 10^{-6} \end{array}

Nichrome's resistivity, about 64 times copper's, makes it the usual choice for heating elements. Good insulators have resistivities more than \(10^{20}\) times larger than copper's.

Worked example: a copper wire in SI

A copper wire 1.00 mm across and 25.0 m long is at 20 °C. Find its resistance. 1. Radius: \(r = 0.500\) mm \(= 0.500 \times 10^{-3}\) m. 2. Area: \(A = \pi r^2 = \pi (0.500 \times 10^{-3})^2 = 7.854 \times 10^{-7}\) m². 3. Resistance, with \(\rho = 1.724 \times 10^{-8}\) Ω·m for annealed copper:

R = \frac{(1.724 \times 10^{-8})(25.0)}{7.854 \times 10^{-7}} = 0.549\,\Omega

4. Check the size: a few tenths of an ohm for tens of metres of household-size wire is typical, which is why short connecting leads are usually treated as having no resistance.

Circular mils

US wire tables use English units built around the round wire. A mil is one thousandth of an inch, and a circular mil (CM) is the area of a circle 1 mil in diameter. The unit is chosen so that the area of a round wire in circular mils is just its diameter in mils, squared:

A_{\text{CM}} = (d_{\text{mils}})^2

No factor of \(\pi\) is needed. Resistivity is then stated in CM·Ω/ft, with \(l\) in feet; for annealed copper at 20 °C it is 10.37 CM·Ω/ft, and for aluminium about 17. The same formula, \(R = \frac{\rho l}{A}\), applies, provided all three quantities use these units together.

Worked example: a run of 14 AWG cable

A copper conductor of size 14 AWG has a diameter of 64.1 mils. Find the resistance of a 500 ft length at 20 °C. 1. Area: \(A = (64.1)^2 \approx 4110\) CM. 2. Resistance:

R = \frac{(10.37)(500)}{4110} = 1.26\,\Omega

3. Check against the wire table: 14 AWG copper is listed at about 2.53 Ω per 1000 ft, so 500 ft gives \(\frac{2.53}{2} \approx 1.26\) Ω. 4. Interpret: a 500 ft circuit run needs a conductor out and another back, so the loop is 1000 ft and its resistance about 2.53 Ω, enough to cause a noticeable voltage loss at high current.

The American Wire Gauge

The American Wire Gauge (AWG) numbers wire sizes so that a larger number means a thinner wire. The steps are geometric:

\begin{array}{lll} \text{AWG} & \text{CM} & \Omega/1000\,\text{ft} \\ 10 & 10{,}380 & 0.999 \\ 12 & 6{,}530 & 1.59 \\ 14 & 4{,}110 & 2.53 \\ 22 & 642 & 16.1 \end{array}

for solid copper at 20 °C. Two rules of thumb follow from the steps. Every 3 gauge numbers roughly halves the area and so doubles the resistance per length. Every 6 gauge numbers roughly halves the diameter. Also, 10 AWG copper is close to 1 Ω per 1000 ft. In US homes, 14 AWG and 12 AWG copper are the common sizes for 15 A and 20 A branch circuits; the electrical code sets the permitted sizes.

Metric units and sheet resistance

Engineers working with semiconductors and printed films often quote resistivity in ohm-centimetres: copper's is \(1.72 \times 10^{-6}\) Ω·cm, since 1 Ω·m \(= 100\) Ω·cm. For a thin film of thickness \(t\), the useful quantity is the sheet resistance \(R_s = \frac{\rho}{t}\), quoted in ohms per square (Ω/□). A strip of length \(l\) and width \(w\) then has

R = R_s \frac{l}{w}

The ratio \(\frac{l}{w}\) counts how many squares fit along the strip. Any square of the film has the same resistance, \(R_s\), whatever its size, because doubling its side doubles both the length and the width.

Worked example: a thin-film resistor

A nichrome film 100 nm thick is patterned into a strip 2.00 mm long and 0.100 mm wide. Find its resistance. 1. Sheet resistance: \(R_s = \frac{\rho}{t} = \frac{1.10 \times 10^{-6}}{100 \times 10^{-9}} = 11.0\) Ω/□. 2. Number of squares: \(\frac{l}{w} = \frac{2.00}{0.100} = 20.0\). 3. Resistance: \(R = 11.0 \times 20.0 = 220\) Ω. 4. Check with the full formula: \(A = wt = (0.100 \times 10^{-3})(100 \times 10^{-9}) = 1.00 \times 10^{-11}\) m², and \(\frac{(1.10 \times 10^{-6})(2.00 \times 10^{-3})}{1.00 \times 10^{-11}} = 220\) Ω, which agrees. 220 Ω is a standard value, so this strip could serve as a real resistor on a chip.

Linking the two systems

The English and SI forms are the same law in different units, and converting one resistivity into the other is a good check. One circular mil is \(\frac{\pi}{4}(0.001 \times 0.0254\,\text{m})^2 = 5.067 \times 10^{-10}\) m², and one foot is 0.3048 m. So copper's 10.37 CM·Ω/ft becomes

\frac{10.37 \times 5.067 \times 10^{-10}}{0.3048} = 1.724 \times 10^{-8}\,\Omega\,\text{m}

which matches the SI table. When a problem mixes units, convert everything into one system before using \(R = \frac{\rho l}{A}\).

Common mistakes to avoid

First, using the diameter where the formula \(A = \pi r^2\) needs the radius, which makes the area four times too big. Second, forgetting that 1 mm² is \(10^{-6}\) m², not \(10^{-3}\) m². Third, applying \(\pi/4\) to a circular-mil area: in CM, the area is simply the diameter in mils squared. Fourth, mixing SI resistivity with feet or circular mils. Fifth, reading AWG backwards: 22 AWG is much thinner than 12 AWG. Sixth, forgetting that a circuit needs a return conductor, so the loop is twice the run length.

Key takeaways

Resistance R = ρl/A rises with length and falls with area; resistivity ρ is a material property, 1.72 × 10⁻⁸ Ω·m for copper at 20 °C. In US wire tables, area in circular mils is the diameter in mils squared, and copper's resistivity is 10.37 CM·Ω/ft. Higher AWG numbers are thinner wires; 3 gauges halve the area, and 10 AWG copper is about 1 Ω per 1000 ft. Thin films use sheet resistance R_s = ρ/t in ohms per square, with R = R_s × l/w. Keep every quantity in one unit system.

Flashcards

Flashcard

Resistance R

Opposition to current, in ohms (Ω)

Caused by collisions with the lattice.

Test your understanding

Question 1 of 5

An aluminium conductor (ρ = 2.82 × 10⁻⁸ Ω·m) is 200 m long with a cross-sectional area of 2.5 mm². What is its resistance?

Question 2 of 5

A copper wire is replaced by one of the same metal that is twice as long and has half the diameter. By what factor does the resistance change?

Question 3 of 5

A copper wire 0.0508 in across and 300 ft long is at 20 °C. What is its resistance? (Copper: 10.37 CM·Ω/ft.)

Question 4 of 5

A run uses 12 AWG copper. If 9 AWG copper is used instead, about how does the resistance of the run change?

Question 5 of 5

A film has a sheet resistance of 50 Ω per square. What is the resistance of a strip 1.0 mm long and 0.25 mm wide?

← Previous topicNext topic →