Electrical Engineering › Section Z · AC motors › Topic Z.2

Synchronous motors, synchronous condensers, and reluctance motors

A synchronous motor turns in exact step with the supply frequency, whatever its load, and by adjusting its field it can even correct a plant's power factor. Reluctance motors reach the same lock-step with nothing on the rotor but shaped iron.

Locked to the supply

Most motors slow a little as their load grows. A synchronous motor does not: its rotor turns at exactly the speed of the stator's rotating field, set only by the supply frequency and the number of poles. Small single-phase versions drove mains clocks and timers for decades, because the grid's average frequency is held very accurately. Large three-phase versions drive compressors, pumps and mills that need constant speed; they are typically a few percent more efficient than induction motors, and their power factor can be adjusted.

The rotating field and synchronous speed

The stator is wound like that of the generator in "Polyphase systems and the three-phase generator", but fed with three-phase currents, which produce a field of constant strength rotating round the air gap. The rotor carries its own poles: permanent magnets, or in large motors a dc winding fed through slip rings or from a brushless exciter. Opposite poles attract, so the rotor locks onto the rotating field. With P poles the field advances one pole pair per cycle, so in rpm

n_s = \frac{120f}{P}

the generator relation \(f = Pn/120\) rearranged. At 60 Hz, 2, 4, 6 and 12 poles give 3,600, 1,800, 1,200 and 600 rpm; at 50 Hz, 3,000, 1,500, 1,000 and 500 rpm.

Worked example: poles for a clock motor

A clock mechanism needs its motor to turn at 600 rpm. 1. On 60 Hz, \(P = 120f/n_s\) gives \(P = 120 \times 60/600 = 12\) poles. 2. On 50 Hz: \(P = 120 \times 50/600 = 10\) poles. 3. Check: \(n_s = 120 \times 50/10 = 600\,\text{rpm}\), 10 revolutions per second, one per five cycles. 4. Clock motors get many poles cheaply from one coil with interleaved steel tabs. 5. If the 12-pole motor were moved to a 50 Hz supply it would run at 500 rpm, and the clock would lose 10 minutes every hour.

Load angle and pull-out torque

At no load the rotor poles line up with the stator field. Add load and the rotor falls back by a load angle \(\delta\), measured in electrical degrees, yet still turns at synchronous speed. For a round rotor, with constant field current and supply voltage and with winding resistance neglected, the torque is

T = T_{max}\sin\delta

Torque peaks at \(\delta = 90^\circ\). Ask for more and the rotor slips a pole, loses synchronism and stops producing steady torque; this is pulling out of step, and protection trips the motor. Drive the shaft forward instead, so that the rotor leads the field, and the same machine becomes a generator, feeding power back to the line; almost all power-station generators are synchronous machines.

Worked example: how far the rotor falls back

A 4-pole synchronous motor has a pull-out torque of 2.5 times its rated torque. 1. At rated load: \(\sin\delta = 1/2.5 = 0.400\), so \(\delta = 23.6^\circ\) electrical. 2. Mechanical angle: one electrical cycle spans two poles, so divide by \(P/2 = 2\), giving \(11.8^\circ\) of shaft rotation. 3. At 1.5 times rated torque: \(\sin\delta = 0.600\), so \(\delta = 36.9^\circ\) electrical. 4. Above 2.5 times rated torque no angle satisfies the equation, so the motor pulls out. Throughout, the speed stays exactly 1,800 rpm on 60 Hz.

Starting a synchronous motor

From a fixed 50 or 60 Hz supply, a synchronous motor cannot start by itself. Its field sweeps past the standing rotor so fast that the pull on the rotor poles reverses every half cycle, averaging zero. Large motors therefore carry a damper (amortisseur) winding, copper bars shorted at the ends in the rotor face, so they start as induction motors. Near synchronous speed the dc field is switched on and the rotor pulls into step. Alternatives are a small starting motor or an electronic drive that ramps the frequency up from zero. Single-phase clock motors often have an induction cup on the rotor for self-starting.

Field current and power factor

At fixed load, the dc field current sets the motor's power factor. At one value, normal excitation, the stator current is at its minimum and in phase with the voltage. With less field current, under-excited, the motor draws magnetising current from the line and runs at a lagging power factor. With more, over-excited, it runs at a leading power factor and supplies reactive power to the line, like a capacitor bank. Plotting stator current against field current at constant load gives the V curve, lowest at unity power factor. Over-excited motors can thus offset a plant's lagging induction-motor load.

Worked example: a synchronous condenser

A synchronous motor run with no mechanical load, purely to adjust reactive power, is a synchronous condenser. A plant on 480 V three-phase takes 500 kW at 0.72 lagging; raise it to 0.95 lagging, neglecting the condenser's own losses. 1. Now: \(Q_1 = 500\tan(\cos^{-1}0.72) = 482\,\text{kVAR}\). 2. Target: \(Q_2 = 500\tan(\cos^{-1}0.95) = 164\,\text{kVAR}\). 3. The over-excited condenser must supply 318 kVAR, so in signed form \(Q_C = -318\,\text{kVAR}\). 4. Line current falls from \(694\,\text{kVA}/(\sqrt{3} \times 480) = 835\,\text{A}\) to \(526\,\text{kVA}/(\sqrt{3} \times 480) = 633\,\text{A}\). As in "Power-factor correction", the load itself is unchanged.

Condensers on the grid

Utilities place large synchronous condensers along long lines and at substations. Unlike a fixed capacitor bank, a condenser's reactive power varies smoothly, in either direction, with its field: it supplies reactive power over-excited and absorbs it under-excited. When voltage sags during a fault it raises its leading current at once, helping hold the voltage up, and its spinning mass adds inertia, which is why grids with much wind and solar generation have recently installed new ones. With no shaft load, a large condenser can be sealed and filled with hydrogen, about 7% as dense as air and about seven times as conductive of heat, which cuts windage loss and improves cooling.

Reluctance motors

Iron in a magnetic field moves to make the flux path's reluctance as small as possible. A reluctance motor uses that alone: its rotor is shaped steel, with no winding or magnet. A synchronous reluctance rotor has a preferred low-reluctance direction, so it lines up with the rotating field and runs at synchronous speed; line-started versions need a cage to start and have poor power factor and efficiency, but modern drive-fed designs are efficient. A switched reluctance motor has salient poles on rotor and stator; electronics energise one stator pole pair at a time, timed by rotor position, pulling the nearest rotor poles round. It is simple and rugged, but noisy, with torque ripple and demanding control.

Common mistakes to avoid

First, letting P be pole pairs in \(n_s = 120f/P\); P counts all the poles. Second, expecting a loaded synchronous motor to slow down; it runs at exactly \(n_s\) until it pulls out. Third, saying synchronous motors always have a leading power factor; only over-excitation makes it lead. Fourth, mixing electrical and mechanical degrees for the load angle: divide by \(P/2\). Fifth, expecting a line-fed synchronous motor to start unaided; it needs a damper winding, a starting motor or a variable-frequency drive.

Key takeaways

A synchronous motor turns at exactly n_s = 120f/P rpm, P being the total number of poles: 1,800 rpm for 4 poles on 60 Hz. Load makes the rotor fall back by a load angle δ, with T = T_max sin δ for a round rotor; past 90° electrical it pulls out of step. On a fixed supply it needs help to start, usually a damper winding. Under-excited it runs lagging; over-excited, leading. Unloaded, it is a synchronous condenser, an adjustable source or sink of reactive power. Reluctance motors use shaped iron rotors; switched reluctance motors need precise electronic control.

Flashcards

Flashcard

Synchronous motor

Rotor turns at exactly the speed of the rotating stator field

Speed does not fall with load.

Test your understanding

Question 1 of 5

What is the synchronous speed of an 8-pole synchronous motor on a 60 Hz supply?

Question 2 of 5

A loaded synchronous motor on a 60 Hz supply has its load increased by 20%, still well below pull-out. What happens to its speed?

Question 3 of 5

A round-rotor synchronous motor's pull-out torque is 2.0 times its rated torque. At rated load, what is the load angle?

Question 4 of 5

A synchronous motor drives a constant load. Its dc field current is raised well above the value that gives unity power factor. How does the motor now look to the supply?

Question 5 of 5

A plant takes 300 kW at 0.80 lagging. A synchronous condenser, losses neglected, brings the plant to unity power factor. What is the condenser's signed reactive power Q_C?

← Previous topicNext topic →