Electrical Engineering › Section M · Transformers and polyphase systems › Topic M.6

Polyphase systems and the three-phase generator

Nearly every power station generates three sinusoidal voltages at once, spaced a third of a cycle apart. This topic shows how a generator produces them, why three phases beat one, and how the three voltages always add to zero.

From one phase to several

A single-phase generator produces one sinusoidal voltage as its shaft turns. Add more windings, spaced evenly around the machine, and the same rotation induces several sinusoids at once, each shifted in time from the next: a polyphase generator. Three phases are by far the most common choice, used by almost all commercial power stations. Single-phase supplies have not vanished; homes and small portable generators use them. But a home's single-phase supply is usually taken from one part of a three-phase system rather than generated on its own, and larger loads such as factory motors take all three phases.

Why three phases?

Three-phase systems win on several counts. For the same power, voltage and line loss, a three-wire three-phase line needs roughly 25% less conductor material than a single-phase line, so towers and cables are lighter and cheaper. A balanced three-phase load draws constant total power, not power that pulses twice per cycle, so large motors run smoothly with steady torque. Three-phase currents in suitably placed windings create a rotating magnetic field, which makes three-phase induction motors self-starting; "Polyphase, wound-rotor, and single-phase induction motors" explores this. More phases are possible, and rectifiers sometimes use six or twelve for smoother dc, but three already captures most of the benefit with the fewest conductors.

Inside the generator

A simple three-phase generator has three identical coils fixed in the stator, the stationary outer part, with their axes 120° apart. The rotor, a magnet or a winding fed with dc, is turned by a turbine or engine. As its field sweeps past each coil in turn, it induces a sinusoidal voltage in each. Because the coils have equal turns and see the same rotating field, the three voltages match in amplitude, waveform and frequency. They differ only in timing: each coil is reached a third of a revolution after the last, so each voltage is 120° behind the one before. The coils' two ends are labelled A, B, C and N.

Frequency, poles and speed

A two-pole rotor, one north and one south pole, gives one electrical cycle per revolution. A rotor with P poles gives P/2 cycles per revolution, so with speed n in revolutions per minute:

f = \frac{Pn}{120}

Grid generators turn at an exact synchronous speed to hold the frequency: 60 Hz in the US, and 50 Hz in Europe and much of the world. Steam turbines spin fast with few poles, while water turbines turn slowly and need many poles. Aircraft often use 400 Hz, because higher frequency allows smaller, lighter transformers and machines.

Worked example: poles and speed

1. A four-pole generator turns at 1800 rpm. Its frequency is \(f = 4 \times 1800/120 = 60\,\text{Hz}\). 2. The same machine in a 50 Hz country must turn at \(n = 120f/P = 120 \times 50/4 = 1500\,\text{rpm}\). 3. A hydroelectric generator turns at 100 rpm. To give 60 Hz it needs \(P = 120f/n = 120 \times 60/100 = 72\) poles. 4. Check: poles always come in north-south pairs, so P must be even, and 72 is. A two-pole steam unit, by contrast, turns at 3600 rpm for 60 Hz.

The three voltages and the ABC sequence

Take coil A's voltage as the reference. With the phase sequence ABC used throughout this course, B lags A by 120° and C lags B by another 120°:

\begin{aligned} e_{AN} &= E_m\sin\omega t \\ e_{BN} &= E_m\sin(\omega t - 120^\circ) \\ e_{CN} &= E_m\sin(\omega t + 120^\circ) \end{aligned}

The last line is the same as lagging by 240°. Here \(E_m\) is the peak value, and each phase has rms value \(E_m/\sqrt{2}\). The sequence is the order in which the voltages reach their peaks. Swapping any two lines reverses it to ACB, and that reverses the direction of a three-phase motor, so sequence matters in practice.

Worked example: the instantaneous sum is zero

Each phase is 120 V rms, so \(E_m = 120\sqrt{2} = 169.7\,\text{V}\). Find the three voltages at \(\omega t = 30^\circ\). 1. \(e_{AN} = 169.7\sin 30^\circ = 84.9\,\text{V}\). 2. \(e_{BN} = 169.7\sin(-90^\circ) = -169.7\,\text{V}\). 3. \(e_{CN} = 169.7\sin 150^\circ = 84.9\,\text{V}\). 4. Sum: \(84.9 - 169.7 + 84.9 = 0\), to rounding. The same happens at every instant. Note the pattern: when one voltage is at a peak, the other two are each at half that value with the opposite sign, and when one is zero, the other two are at \(\pm 0.866E_m\).

Phasors that close a triangle

As rms phasors in polar form, with A as reference, the three voltages are \(\mathbf{E}_{AN} = 120\angle 0^\circ\), \(\mathbf{E}_{BN} = 120\angle -120^\circ\) and \(\mathbf{E}_{CN} = 120\angle 120^\circ\) volts. In rectangular form they are \(120\), \(-60 - j103.9\) and \(-60 + j103.9\). Adding the real parts gives 0, and so does adding the imaginary parts. Geometrically, placing the three phasors head to tail closes an equilateral triangle. This zero sum is the property the next topics rely on: it is why a balanced system can share a return path that carries no current.

Constant power from three phases

Connect a 10 Ω resistor across each 120 V phase. A single phase alone delivers \(p = v^2/R\), which swings between 0 and 2880 W twice per cycle, averaging 1440 W. Add the three phases together, though, and the result is steady:

\sin^2\theta + \sin^2(\theta - 120^\circ) + \sin^2(\theta + 120^\circ) = \tfrac{3}{2}

for every angle \(\theta\). The total is therefore \(3 \times 1440 = 4320\,\text{W}\) at every instant, not just on average. A motor on a balanced three-phase supply feels no pulsation in the power it receives, which is one reason large machines are almost always three-phase.

Common mistakes to avoid

First, writing C as lagging A by 120°; in the ABC sequence C lags A by 240°, which is the same as leading A by 120°. Second, mixing peak and rms values: a 120 V phase has a peak of about 170 V. Third, adding phasor magnitudes, 120 + 120 + 120, instead of adding the phasors, which gives zero. Fourth, forgetting the factor 120 in f = Pn/120, or using pole pairs in place of poles. Fifth, assuming the phase sequence does not matter; reversing it reverses a motor.

Key takeaways

A three-phase generator has three identical stator coils 120° apart, so it produces three sinusoids of equal amplitude and frequency, 120° apart in time. With sequence ABC, e_BN lags e_AN by 120° and e_CN lags it by 240°. The instantaneous voltages, and their phasors, always sum to zero. Frequency is f = Pn/120. Three-phase systems need about 25% less conductor material than single-phase for the same power, deliver constant total power to a balanced load, and create rotating fields for self-starting motors. Swapping two lines reverses the sequence and the motor's direction.

Flashcards

Flashcard

Polyphase generator

Produces several sinusoids at once, shifted in time

Three phases is the usual choice.

Test your understanding

Question 1 of 5

A six-pole generator must supply 60 Hz. At what speed must it turn?

Question 2 of 5

With phase sequence ABC and e_AN = E_m sin ωt, which expression gives e_CN?

Question 3 of 5

Each phase of a balanced three-phase generator is 230 V rms. At the instant e_AN is zero and rising, what are e_BN and e_CN?

Question 4 of 5

Three phasors of 120 V rms at 0°, −120° and +120° are added. What is the sum?

Question 5 of 5

A balanced three-phase resistive load takes 4.5 kW on average. What is its total instantaneous power?

← Previous topicNext topic →