Electrical Engineering › Section M · Transformers and polyphase systems › Topic M.5
Nameplate data and transformer types
A transformer's nameplate tells you how much it can safely carry and at what voltages and frequency. Behind that plate sits one of many designs: power, audio, pulse, autotransformer, centre-tapped or multi-winding, each suited to its job.
Reading a nameplate
A typical power-transformer nameplate might read 25 kVA, 7200/240 V, 60 Hz. The 25 kVA is the rated apparent power, \(S = VI\). The two voltages are the rated winding voltages; either side can serve as primary, so the same unit steps 7200 V down to 240 V or 240 V up to 7200 V, with a = 30 or 1/30. The frequency is the one the core was designed for. Plates often add impedance (in percent), insulation class, temperature rise and a wiring diagram. From the kVA and voltage ratings you can find the rated current of each winding, which is the real limit: \(I_\text{rated} = S/V\).
Why the rating is in volt-amperes
Winding heating depends on current, and core flux on voltage. Neither cares whether the load absorbs real power or merely trades reactive power back and forth. Recall from "The power triangle and total P, Q, and S" that a purely capacitive or inductive load draws current while taking zero average power. A rating in watts would let such a load overheat the windings while appearing to use nothing. A rating in volt-amperes limits the product of voltage and current directly, whatever the power factor. So a transformer can be overloaded while its load draws fewer watts than the kVA figure: always compare the load's apparent power, not its real power, with the rating.
Worked example: rated currents and overload
Use the 25 kVA, 7200/240 V transformer. 1. High-voltage winding: \(I = 25{,}000/7200 = 3.47\,\text{A}\). 2. Low-voltage winding: \(I = 25{,}000/240 = 104\,\text{A}\). 3. Now a 240 V load draws 120 A at a power factor of 0.80 lagging. Its real power is \(240 \times 120 \times 0.80 = 23.0\,\text{kW}\), below 25. 4. Its apparent power is \(240 \times 120 = 28.8\,\text{kVA}\), and the current exceeds the 104 A rating. 5. Conclusion: the transformer is overloaded by about 15% despite the watt figure. Power-factor correction, from "Power-factor correction", would cut the current without changing the real power.
Why frequency is on the plate
Rearranging the emf equation from "The iron-core transformer and power transmission" gives \(\Phi_m = E/(4.44fN)\). For a fixed voltage and winding, the peak flux is inversely proportional to frequency. Power transformers are designed to run their cores near the knee of the B-H curve, so there is little headroom. Run a 60 Hz transformer at its rated voltage on a 50 Hz supply and the flux rises by \(60/50 = 1.2\), 20%. The core heads into saturation, the magnetising current rises steeply, and the windings overheat. Running a 50 Hz design on 60 Hz at rated voltage lowers the flux instead, which is generally acceptable.
Types and construction
Power transformers handle mains and distribution frequencies. Audio transformers must pass roughly 20 Hz to 20 kHz evenly. Intermediate-frequency and radio-frequency transformers work at hundreds of kilohertz and above, often with ferrite or air cores. Pulse transformers pass fast-edged pulses, for example to trigger switching devices, without saturating. Iron cores are built from thin laminations, insulated from one another and made of steel with a little silicon added, both of which reduce eddy-current loss. In a core-type design the windings sit on the legs of a rectangular core; in a shell-type design the core surrounds the windings. The schematic symbol shows the core: parallel lines for iron, none for air.
The autotransformer
An autotransformer has a single winding with a tap, so one part is shared by input and output. The voltage ratio still follows the turns, but part of the power passes straight through by conduction and only the rest is transformed magnetically. That lets a small autotransformer handle a large load when the input and output voltages are close. The variable autotransformer, a winding with a sliding contact, gives an adjustable ac voltage on many test benches. The cost is isolation: input and output share a conductor, so the output is never isolated from the supply, and touching it is as dangerous as touching the mains.
Worked example: boosting a sagging supply
A 120 V, 15 A resistive load is fed from a line that has sagged to 108 V. A winding of 108 V in common with the line plus a 12 V series section, connected so that their voltages add, restores 120 V. Assume an ideal transformer. 1. Load power: \(120 \times 15 = 1800\,\text{W}\), so the line current is \(1800/108 = 16.7\,\text{A}\). 2. The series section carries the 15 A load current at 12 V: \(12 \times 15 = 180\,\text{VA}\). 3. The common section carries the difference, \(16.7 - 15 = 1.67\,\text{A}\), at 108 V: also 180 VA. 4. Result: the windings handle only 180 VA to deliver 1800 W. A two-winding transformer doing the same job would need a full 1800 VA rating.
Centre taps and the split-phase supply
A tap at the midpoint of a winding gives two equal halves. The most familiar case is the US residential service: the pole or pad transformer's 240 V secondary has a grounded centre tap, the neutral. Each outer conductor is 120 V from neutral, and the two are 240 V apart, because the halves' voltages are 180° apart as measured from the neutral. Lighting and outlets use 120 V; ranges, dryers and water heaters use 240 V. The neutral carries the difference of the two outer currents: with resistive loads of 15 A on one side and 10 A on the other, it carries 5 A, and with equal loads it carries nothing.
Several secondaries at once
One primary can feed several secondaries, each with its own turns ratio. Every secondary voltage follows its own ratio, \(V_2/V_1 = N_2/N_1\), and the primary supplies their total power. Seen from the primary, each load reflects with its own \(a^2\), and the reflected loads appear in parallel. Example: a 240 V primary feeds a 24 V secondary with 6 Ω and a 12 V secondary with 2 Ω. 1. Ratios: 10 and 20, so the loads reflect as \(100 \times 6 = 600\,\Omega\) and \(400 \times 2 = 800\,\Omega\). 2. In parallel: 343 Ω. 3. Check power: \(240^2/342.9 = 168\,\text{W}\), equal to \(96 + 72\,\text{W}\) in the two loads.
Common mistakes to avoid
First, comparing a load's watts with a kVA rating; compare apparent power, or compare currents with the rated currents. Second, assuming a transformer works on any frequency at rated voltage; a lower frequency raises the flux and can saturate the core. Third, treating an autotransformer or variac output as isolated; it is connected to the supply. Fourth, adding reflected loads from several secondaries in series; they appear in parallel at the primary. Fifth, expecting the neutral of a split-phase supply to carry the sum of the outer currents; it carries their difference.
Key takeaways
A nameplate gives apparent power in VA or kVA, rated winding voltages and frequency; rated current is S/V for each winding. Ratings use volt-amperes because heating depends on current, whatever the power factor. Peak flux is E/(4.44fN), so running below rated frequency at rated voltage risks saturation. Laminated silicon-steel cores cut eddy-current loss. An autotransformer shares one winding, transforms only part of the power and gives no isolation. A centre-tapped 240 V secondary gives the US 120/240 V split-phase service. Several secondaries reflect into the primary in parallel.
Flashcards
Flashcard
Rated apparent power S = VI of a transformer
Test your understanding
Question 1 of 5
A transformer is rated 10 kVA, 2400/240 V. What is the rated current of its 240 V winding?
Question 2 of 5
A 5 kVA, 240 V transformer supplies a load drawing 25 A at a power factor of 0.70 lagging. Is it overloaded?
Question 3 of 5
A transformer designed for 60 Hz is connected to a 50 Hz supply at its rated voltage. What happens to the peak core flux?
Question 4 of 5
What is the main drawback of an autotransformer compared with a two-winding transformer?
Question 5 of 5
A US split-phase service has 20 A of resistive load on one 120 V side and 12 A on the other. What current flows in the neutral?